Das Bild ist mit 'Attribution Required' markiert, aber es wurden keine Informationen über die Attribution bereitgestellt. Vermutlich wurde bei Verwendung des MediaWiki-Templates für die CC-BY Lizenzen der Parameter für die Attribution weggelassen. Autoren und Urheber finden für die korrekte Verwendung der Templates hier ein Beispiel.
Größe:
350 x 171 Pixel (23074 Bytes)
Beschreibung:
photo of electrical Residual-Current Circuit Breaker
  1. incoming terminals
  2. outgoing terminals
  3. reset button
  4. contact
  5. solenoid
  6. sense coil
  7. sense circuitry
  8. test button
  9. test wire


The incoming supply and the neutral conductors are connected to the terminals at (1) and the outgoing load conductors are connected to the terminals at (2). The earth conductor (not shown) is connected through from supply to load uninterrupted.

When the reset button (3) is pressed the contacts ((4) and hidden behind (5)) close, allowing current to pass. The solenoid (5) keeps the contacts closed when the reset button is released.

The sense coil (6) is a differential current transformer which surrounds (but is not electrically connected to) the live and neutral conductors. In normal operation, all the current down the live conductor returns up the neutral conductor. The currents in the two conductors are therefore equal and opposite and cancel each other out.

Any fault to earth (for example caused by a person touching a live component in the attached appliance) causes some of the current to take a different return path which means there is an imbalance (difference) in the current in the two conductors (single phase case), or, more generally, a nonzero sum of currents from among various conductors (for example, three phase conductors and one neutral conductor).

This difference causes a current in the sense coil (6) which is picked up by the sense circuitry (7). The sense circuitry then removes power from the solenoid (5) and the contacts (4) are forced apart by a spring, cutting off the electricity supply to the appliance.

The device is designed so that the current is interrupted in a fraction of a second, greatly reducing the chances of a dangerous electric shock being received.

The test button (8) allows the correct operation of the device to be verified by passing a small current through the orange test wire (9). This simulates a fault by creating an imbalance in the sense coil. If the RCD does not trip when this button is pressed then the device must be replaced.
Lizenz:
Bild teilen:
Facebook   Twitter   Pinterest   WhatsApp   Telegram   E-Mail
Weitere Informationen zur Lizenz des Bildes finden Sie hier. Letzte Aktualisierung: Tue, 09 Jan 2024 09:58:42 GMT

Relevante Bilder

© Raimond Spekking / CC BY-SA 4.0 (via Wikimedia Commons)
© Raimond Spekking / CC BY-SA 4.0 (via Wikimedia Commons)

Relevante Artikel

Fehlerstrom-Schutzschalter

Fehlerstrom-Schutzschalter sind die am häufigsten verwendeten Geräte aus der übergeordneten Gruppe der Fehlerstrom-Schutzeinrichtungen. In den älteren, umgangssprachlich noch üblichen Bezeichnungen FI-Schutzschalter oder FI-Schalter steht „F“ für das Wort Fehler und „I“ für das Formelzeichen der elektrischen Stromstärke. Durch die Harmonisierung in der Normung auf internationaler Ebene wird seit 2008 allgemein die Bezeichnung RCD auch in den deutschsprachigen Normen und der Literatur verwendet. .. weiterlesen